UPS30603 - Meissner, MP3060, 60KVA, 28-35mins, 400V/400V
- True on-line double conversion design
- Intelligent LCD display
- Very low output distortion
- IGBT, PWM technology
- 100% unbalanced load capability
- Separate battery charging circuit for increased battery life
- Locally designed, manufactured and serviced
- Static and maintenance bypass facilities are standard
- d.c. Isolator for battery protection
- Robust, true on-line protection for computer and industrial application
The UPS30603 is designed to provide high quality continuous power. Solid state true on-line technology is used in the MP3000 UPS with pulse width modulated (PWM) control to protect critical loads against power sags, surges, brown-outs and power failure. The MP3000 UPS inverter uses IGBT switching elements which together with PWM ensures close tolerance output voltage irrespective of variations in input voltage or output load. A fully intelligent monitoring system is incorporated on all MP3000 UPS systems, offering the ability to interact with customer alarms, serial interface allowing hard wired connection to a local computer and simple network management protocol (SNMP) compatible software available for most operating platforms.
Model | MP3040 | MP3060 | MP3080 | M3100 | MP3125 |
Input | |||||
Voltage | 400V / 415V, 3 Phase, 4 Wire | ||||
Tolerance | +10% – 15% | ||||
Frequency | 50Hz or 60Hz ± 5% | ||||
Charger d.c. Voltage Regulation | ± 1% | ||||
d.c. Ripple Voltage | Less than 1% | ||||
Inverter Output | |||||
Rated Output at 0.8PF | 40kVA (32kW) | 60kVA (48kW) | 80kVA (64kW) | 100kVA (80kW) | 125kVA (100kW) |
Load Power Factor Range | From 0.6 IND to unity within kW rating | ||||
Rated Output Voltage | 400 / 230V or 415 / 240V, 3-Phase, 4 wire | ||||
Regulation No Load to Full Load (Steady State) | ±1% | ||||
Voltage Regulation with 100% Load Application | ±5% | ||||
Regulation with 100% Unbalanced Load | ±1% Phase Voltage Regulation | ||||
Phase Displacements at 100% Unbalanced Load | 120° ± 2.5% | ||||
Recovery Time to Steady State | Less than 5 milliseconds | ||||
Overload Capability | 150% for 10 sec. / 105% for 30 min | ||||
Crest Factor Ratio (Peak / RMS Current) | 3:1 | ||||
Total Harmonic Distortion (Full Load – Linear) | Less than 5% (typically 3%) | ||||
Frequency | |||||
Free Running | 50Hz or 60Hz ± 0.05% | ||||
Synchronised with Mains | 50Hz or 60Hz ± 2% (adjustable) | ||||
Static Transfer Switch | |||||
Transfer Time | No Break | ||||
Overload Rating 100ms | 1000% | ||||
General | |||||
Efficiency (Input to Output) | 89% | ||||
Lightning Protection | Designed to withstand standard test impulses of 6kV and 3kA | ||||
Environment | |||||
Acoustic Noise Level | Less than 55dBA at 1 meter | ||||
Operating Temperature Range | 0 – 40ºC | ||||
Relative Humidity (Non-Condensing) | 95% | ||||
Battery | |||||
Type | Lead Acid Maintenance Free | ||||
Anticipated Life | 3 to 5 years depending on number of discharges and temperatures | ||||
Monitoring | |||||
Front Panel | Intelligent LCD Panel | ||||
Voltage Free Contacts | Voltage free contacts available for remote monitoring by a remote alarm panel or building management system + DB9 | ||||
Remote Alarm Panel | Available as an option extra | ||||
Dimensions (mm) and Weight (kg) | |||||
UPS Cabinet | 40kVA | 60kVA | 80kVA | 100kVA | 125kVA |
Width | 800 | 800 | 1 400 | 1 400 | 1 400 |
Depth | 700 | 700 | 750 | 750 | 750 |
Height | 1 800 | 1 800 | 1 800 | 1 800 | 1 800 |
Weight (approx.) | 700 | 760 | 900 | 1 200 | 1 250 |
Battery Cabinet (with approx. 10min. battery) | |||||
Width | 750 | 750 | 1 500 | 1 500 | 1 500 |
Depth | 750 | 750 | 750 | 750 | 750 |
Height | 1 800 | 1 800 | 1 800 | 1 800 | 1 800 |
Weight (approx.) | 577 | 705 | 1 154 | 1 410 | 2 024 |