RT-2K - Delta Electronics, RT Series, 2KVA, 0-320mins, 230V/230V
- True online double-conversion topology and zero transfer time to battery ensure high reliability
- Watch-dog design of DSP (Digital Signal Processor) increases reliability
- Cold-start capability provides temporary battery power when the utility power is out
- Fan failure detection alerts users to failed fans
- Hot swappable batteries ensure continuous operation even when batteries are being replaced
- Optional external battery pack for easy scaling of longer backup time
- Operation temperature tolerance up to 50°C ensures critical loads’ continuity
- High output power factor 0.9 provides more real power to critical loads
The RT-2K is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. The Amplon RT 1-3kVA series features an output power factor of 0.9 and best-in-class AC-AC efficiency up to 94% resulting in greater energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.
Model | RT-1K | RT-2K | RT-3K |
Power Rating | 1kVA/0.9kW | 2kVA/1.8kW | 3kVA/2.7kW |
Input | |||
Nominal Voltage | 200*/208*/220/230/240Vac | ||
Voltage range | 175~280Vac (full load); 120~175Vac (70~100% load) | ||
Frequency | 40~70Hz | ||
Power Factor | > 0.99 (full load) | ||
Current Harmonic Distortion | < 5% | ||
Output | |||
Power Factor | 0.9 | ||
Voltage | 200*/208*/220/230/240Vac | ||
Voltage Regulation | ± 1% (linear load) | ||
Frequency | 50/60Hz ± 0.05Hz | ||
Voltage Harmonic Distortion | < 2% (linear load) | ||
Overload Capability | < 105%: Continuous; 105~125%: 1 minute; 125~150%: 15 seconds | ||
Receptacle | IEC C13 x 6 | IEC C13 x 6, IEC C19 x 1 | |
Efficiency | |||
AC-AC | 90% | Up to 94% | |
ECO Mode Battery Volt | 96% | Up to 97% | |
Battery | |||
Battery Voltage | 24Vdc | 48Vdc | 72Vdc |
Typical Backup Time** | 6.5 minutes | 7 minutes | |
Charge Current | 1.5A | 2A | |
Recharge Time | 3 hours to 90% | ||
Audible Noise | < 40dB | < 43dB | < 46dB |
Display | LCD display and LED indicators | ||
Interfaces | SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1 | ||
Conformance | CE, TISI, RCM, EAC | ||
Dimensions (W x D x H) | |||
UPS | 440 x 335 x 89mm | 440 x 432 x 89mm | 440 x 610 x 89mm |
External Battery Pack | 440 x 335 x 89mm | 440 x 432 x 89mm | 440 x 610 x 89mm |
Weight | |||
UPS | 12kg | 18kg | 28kg |
External Battery Pack | 15kg | 27kg | 44kg |
Environment | |||
Operating Temperature | 0~50°C*** | ||
Relative Humidity | 5~95% (non-condensing) |