RT-10K - Delta Electronics, RT Series, 10KVA, 0-320mins, 230V/230V
- True online double-conversion topology and zero transfer time to battery ensure high reliability
- Watch-dog design of DSP (Digital Signal Processor) increases reliability
- Cold-start capability provides temporary battery power when the utility power is out
- Fan failure detection alerts users to failed fans
- Hot swappable batteries ensure continuous operation even when batteries are being replaced
- Optional external battery pack for easy scaling of longer backup time
- Operation temperature tolerance up to 50°C ensures critical loads’ continuity
- High output power factor 0.9 provides more real power to critical loads
The RT-10K is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. The Amplon RT 5-6kVA series features an output power factor of 0.9 and best-in-class AC-AC efficiency up to 92% resulting in greater energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.
Model | RT-5K | RT-6K | RT-10K |
Power Rating | 5kVA/4.5kW | 6kVA/5.4kW | 10kVA/9kW |
Input | |||
Nominal Voltage | 200/208/220/230/240 Vac (single phase) | ||
Voltage Range | 100~300Vac | ||
Current Harmonic Distortion | < 5% (full load) | ||
Power Factor | > 0.99 (full load) | ||
Frequency | 40 ~ 70 Hz | ||
Electrical Connection | Terminal block | ||
Output | |||
Voltage | 200/208/220/230(default)/240 Vac (single phase) | ||
Voltage Harmonic Distortion | < 2% (linear load) | ||
Voltage Regulation | ± 1% (static) ± 2% (typical) | ||
Frequency | 50 or 60 ± 0.05 Hz | ||
Overload Capability | 106 ~ 110%: 10 minutes 111 ~ 125%: 5 minutes 126 ~ 150%: 30 seconds | ||
Electrical Connection | Terminal block | ||
Crest Factor | 3:1 | ||
Battery & Charger | |||
Nominal Voltage | 192 Vdc | 192 Vdc | 240 Vdc |
Charge Current | Built-in: maximum 4A (adjustable) Additional charger board (optional): maximum 4A (internal installation) | ||
Electrical Connection | Exclusive cable | ||
Interface | |||
Standard | RS232 x 1, SNMP slot x 1, Smart slot x 1, Parallel port x 1 | ||
Conformance | |||
Safety & EMC | CE, TUV, EN62040-1 CISPR 22 Class A | ||
Other Features | |||
Parallel Redundancy | 1+1 | ||
Remote Control | REPO, Remote On/Off | ||
Common Battery Installation | Yes | ||
Efficiency | |||
AC-AC | 92% (full load) | ||
ECO Mode | 96% (full load) | ||
Environment | |||
Operating Temperature | 0 ~ 40ºC | ||
Relative Humidity | 0 ~ 95% (non-condensing) | ||
Audible Noise(at one meter) | 54 dBA | ||
Physical | |||
UPS Dimensions (WxDxH) | 440 x 671 x 89mm | 440 x 671 x 89mm | 440 x 623 x 131mm |
Battery Pack Dimensions (WxDxH) | 440 x 638 x 89mm | 440 x 638 x 89mm | 440 x 595 x 131mm |
UPS Weight | 15kg | 15.5kg | 21.3kg |
Battery Pack Weight | 36kg | 36kg | 66kg |