Automate and Power Your Business

UPS0530R01

UPS0530R01 - Meissner, MP230, 30KVA, 8-10mins, 400V/230V

The UPS0530R01 use a microprocessor controlled design using advanced high frequency pulse width modulated (PWM) techniques. The result is a compact, low component count UPS providing unequaled reliability and performance with very low noise levels. Our MP200 UPS range is packaged in a aesthetically pleasing cabinet with standard batteries housed within the UPS cabinet. A separate matching battery cabinet is available for extended run-times. The Meissner MP200 UPS is a true on-line design incorporating a static bypass switch as standard. In addition to this a manual make-break-switch is also provided for additional system reliability and ease of maintenance. The alarms and the on/off switch on the UPS is incorporated into the front facia of the unit. Standard protection is provided to reduce possible damage caused by lightning strikes. PLC Group supplies the entire range of MP200 UPS systems to the industry.

  • True double conversion on-line design
  • Available in single and three phase input
  • Maintenance Bypass Switch on all models
  • Static Bypass Switch as standard
  • High Frequency Pulse Width Modulated (PWM) microprocessor design
  • High overload capability
  • Very quiet operation (typically 55dBA and lower)
  • Compact, slimline cabinet on castors for easy installation
  • Simple Network Management
  • Protocol (SNMP) capability
  • Extended back-up options available
  • Solid, reliable on-line double conversion back-up for mission critical application
ModelMP208MP210MP215MP220MP225MP230
Input
Voltage400V / 230V400V
 3 Phase or 1 Phase ±15%3 Phase ±15%
Input Frequency*50Hz or 60Hz ±15%
Charger d.c. Voltage Regulation±1%
d.c. Ripple VoltageLess than 1%
Output
Rated Output8kVA (6.4kW) 10kVA (8kW)15kVA (10.5kW)20kVA (14kW)25kVA (17.5kW)30kVA (21kW)
Power Factor 0.8PF lagging0.7PF lagging
Load Power Factor RangeFrom 0.6 IND to unity within kW rating
Rated Output Voltage ( I Phase)230V
Regulation No Load to Full Load (Steady State)±1%
Voltage Regulation with 100% Load Application±5%
Recovery Time to Steady State30 milliseconds
Overload Capability110% for 30 seconds
Crest Factor Ratio (Peak / RMS Current)3:1
Total Harmonic DistortionLess than 5% (typically 3% for linear loads)
Frequency – Free Running*50Hz or 60Hz ±0.2%
Frequency – Synchronised with Mains*50Hz or 60Hz ±2% (adjustable)
Static Transfer Switch
Transfer TimeNo Break
Overload Rating 100ms1000%
General
Efficiency (Input to Output)87%
Lightning ProtectionDesigned to withstand standard test impulses of 6kV and 3kA
Environment
Acoustic Noise LevelTypically 55dBA at 1 meter
Operating Temperature Range0 – 40ºC
Relative Humidity (Non-Condensing)95%
Battery
Blocks16x12V blocks22x12V blocks32x12V blocks
Type – InternalLead Acid Maintenance Free
Anticipated Life3 to 5 years depending on number of discharges and temperatures
Standard Discharged Times (Mins)  10 (Other battery times or types available on request)
Dimension (mm) W x D x H
UPS Cabinet Only440 x 750 x 1000
Battery Cabinet A440 x 750 x 1000
Battery Cabinet B585 x 750 x 1000
Weight (Kg)
UPS Cabinet240240320400420500
Battery Cabinet Typical280
Interfaces
StandardComputer Interface. True intelligent RS-232
OptionalRelay contacts and remote alarm panel with AS400 interface
SoftwareAvailable on request / SNMP Capable
Note: The 8kVA and 10kVA units are also available in 110V input and 110V output