HPH-100K

HPH-100K - Delta Electronics, HPH Series, 100KVA, 0-320mins, 400V/400V

The HPH-100K is a great solution for small and medium data centers and mission critical applications requiring highly reliable power protection and unbeatable energy efficiency. The innovation behind the Ultron HPH Series UPS design incorporates low iTHD (<3%), 96% AC-AC and 99% ECO mode energy efficiency for increased Total Cost of Ownership (TCO) savings. Fully rated power (kVa=kW) without de-rating, the Ultron UPS offers leading AC-AC efficiency without sacrificing any available power requirements. Increased availability is further augmented through Ultron HPH watch-dog design. Quite simply, the HPH Series UPS from Delta is a best-in-class (three phase 20/30/40/60/80/100/120 kVA UPS) power protection system that combines maximum available power, unsurpassed energy efficiency, and superior power performance with a significant advantage: TCO savings. HPH is an ideal choice for datacenters as well as for industries involved in factory equipment, communication systems, computer network systems, medical systems, monitoring systems and more. Since the Ultron HPH series UPS was launched in 2013, it has obtained wide adoption by customers and professional organizations worldwide, such as HPH 20kVA and 30kVA UPS for the luxury car manufacturers in Germany, key telecommunication operators in Asia, and international medical equipment providers in India, to name a few.

  • Fully rated power (kVA=kW) for maximum power availability
  • Leading AC-AC efficiency up to 96% saves energy costs
  • Low harmonic pollution (iTHD<3%) and high input power factor (>0.99) reduce upstream investment costs
  • Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
  • Redundant auxiliary power and fan design* enhance system reliability
  • Optional external battery pack for easy scaling of longer backup time
  • Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
  • A wide choice of configurations, such as N+X redundancy and hot stand-by
  • Flexible battery configuration optimizes battery investment
  • Multi-connectivity interface supports remote UPS monitoring and management
ModelHPH-60KHPH-80KHPH-100KHPH-120K
Power Rating60kVA/60kW80kVA/80kW100kVA/100kW120kVA/120kW
Input
Nominal Voltage380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)
Voltage range332~477 Vac (full load), 228~332 Vac (63~100% load)
Frequency40~70 Hz
Power Factor> 0.99 (full load)
Current Harmonic Distortion< 3%
Output
Power Factor1
Voltage380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)
Voltage Regulation± 1%
Frequency50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion< 2% (linear load)
Overload Capability
≤ 105%: continuous
106~≤ 125%: 10 minutes
126~≤ 150%: 1 minute
> 150%: 1 second
 
Efficiency
AC-AC> 96% (HPH-40K-120K efficiency is tested by TÜV)
ECO ModeUp to 99%
Battery
Battery Voltage240 Vdc
Battery TypeSupport SMF/VRLA/Tubular/Ni-Cd
Quantity32~46 pcs
Charge Current10A15A20A20A
Communication Interface
All ModelsSMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1 
Conformance
SafetyCE, RCM
UPS Classification According to IEC 62040-3VFI-SS-111
Dimensions (W x D x H)
UPS520 x 800 x 1175 mm520 x 800 x 1175 mm520 x 800 x 1760 mm520 x 800 x 1760 mm
Weight
UPS186.5kg191kg86.5kg312kg
Environment
Operating Temperature0~40˚C
Relative Humidity5~95% (non-condensing)
Audible Noise< 65 dB
Other Features
Parallel RedundancyUp to 4 units
Emergency Power OffYes (local and remote)
Maintenance Bypass SwitchYes